3 Attempt Automatic Generator Control Module AECM107
with remote/wired/local start/stop function
Suitable for single and three phase generators.
Not suitable for petrol generators with manual choke.
DESCRIPTION
The Model AECM107 is an Automatic Generator Control Module designed to automatically [remotely] or manually start and stop the engine. It will indicate the operational status and fault conditions, automatically shut down the engine and indicate the start engine failure by flashing "START FAIL" LED on the front panel. Other faults are indicated by steady LED
For wired remote control: toggle switch is in “OFF” position; remote start [input 1] is linked to battery negative;
For local control: front switch is in “ON” position; [input 1] is unused.
0.5 Second after the fuel relay is energized [terminal 5], the 3 attempt start will begin its start sequence: the start relay will energize, feeding battery +ve (on terminal 7 to terminal 2 and thence on to the start circuit. If the engine has not fired by the end of 1st attempt, the starter is turned off for a resting period. The sequence will then repeat up to a maximum number of start attempts. Following a successful start, sensed when AC alternator's voltage rises above 40% of nominal, the start relay is de-energized and latched out to prevent reengagement of the starter with the engine running.
WIRЕLESS CONTROL
Toggle switch is in OFF position.
Terminal 1: (wired remote start is unused)
Make sure there are no metal doors/walls/other metal shields between you and controlled generator. Any metal obstacle can significantly reduce the working distance between the remote control device (кеу fоb) and controlled generator. Press the wirеlеss controller button A to start and run the engine. Press wirеlеss controller button A again to stop. Button B is acting the same way as an Emergency Stop input 4. If button B is pressed, the controller becomes inactive and cannot be used until the button B is pressed again. Please note that the shape of the supplied key fob may differ from the one shown in the picture, but it will have the same functionality and approximate size.
For wired remote start: toggle switch is in “OFF” position, pre-heat enabler [DIP switch 2] is ON, remote start [input 1] is linked to battery negative;
For local start: pre-heat enabler [DIP switch 2] is ON, toggle switch is in “ON” position;
For wireless start: toggle switch is in “OFF” position, pre-heat enabler [DIP switch 2] is ON, remote wired start [input 1] is unused;
When 10 second pre-heating cycle is timed out and flashing LED on the panel is turned off, the module will begin its start sequence: the fuel solenoid relay is energised feeding battery +ve on terminal 7 to terminal 5 and thence to the fuel solenoid circuit, the start relay will energise, feeding battery +ve on terminal 7 to terminal 2 and thence on to the start circuit. If the engine has not fired by the end of 1st attempt, the starter is turned off for a resting period. The sequence will then repeat up to a maximum number of start attempts. Following a successful start, sensed when AC alternator's voltage rises above 40% of nominal, the crank relay is de-energised and latched out to prevent re-engagement of the starter with the engine running.
LOAD CONTROL (optional, not included)
After a successful start, when engine's parameters are settled (when 7 sec time delay provided by hold-off timer is timed out), the Load Control Output will energize and send a signal from terminal 10 to an external power relay. This energizes a contactor which will connect the AC alternator output to the load. The run time before accepting load and the run time after relieving load (while generator is still running and is ready to accept the load again if the remote/local start signal is switched back on) are reprogrammable with a limit of 255 sec [4.25 min] max.(for each timer).
Should the engine still fail to start after the maximum number of attempts, START FAIL is displayed and the starter is latched out until reset via “OFF” position of toggle switch or via terminal 1 / key fob if the engine start was initially made via remote start signal.
NOTE
The starter relay can only energize for 2nd and 3rd crank cycle if “Low Oil Pressure” is sensed, to confirm that the engine is stationary. This is designed to prevent damage to the starter and ring gear in the event of the control module not sensing that the engine has started (i.e. terminals 11 and 12 are not connected properly to the alternator AC output). Should the engine still fail to start after the maximum number of attempts, “START FAIL” is displayed and the starter is latched out until reset via “OFF” position of toggle switch or via terminal 1 if the engine start was initially made via remote start signal.
Relay outputs are provided for:
The relays supply positive plant supply out.
Configurable inputs are available for:
The AECM107 series modules have been designed for DIN rail and/or flat surface panel mounting.
Wiring diagram
AECM107 SPECIFICATION
DC Supply (engine starting battery): 12V or 24V ( 8...40Vdc )
Max. Standby Current: 10 mA @ 12 V
Alternator Input Range: 300 VAC max
Under speed shutdown: @ 30 Hz [45Hz for USA and Canada]
Over speed shutdown: @ 57 Hz [69Hz for USA and Canada]
Number of attempts: 3
Crank duration: 12 sec (max.) self-regulated
Preheat time: 10 sec (optional)
Load on time delay: 10 sec (optional)
Load off time delay: 10 sec (optional)
Hold-off timer set for: 7 sec
Starter output (terminal 2): 20A max
Fuel output (terminal 5): 20A max
Pre-heat output (terminal 9): 20A max (optional)
Load control output (terminal 10): 20A max (optional)
Dimensions: 95 X 90 X 40 mm (exc. flanges)
Operating Temperature Range: -30 to +70°C.
For internal use only.
All settings are user-configurable prior to shipment.
All optional inputs / outputs available at extra cost, please contact us if you need a pre-heat function, battery voltage sensor (BVS) or load control output.
Package Includes:
1x AECM107 controller with wirеlеss rеcеiver built-in
1x кеу fоb may come without battery, please fit type 23A 12V battery
1x Wiring diagram/manual
The DIN rail is not included